Appendix c: alarms and relays, Alarm relays, Alarms – GE Industrial Solutions CPS6000 User Manual

Page 197: Alarm relays alarms

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

197

Appendix C: Alarms and Relays

Alarm Relays

The control unit is provided with six alarm relays; four to provide the actual alarm condition,
and two to provide the severity associated with the alarm. The severity relays transmit the
either PMJ or PMN. Each alarm is factory assigned a severity based on industry practices,
however, they may be reassigned to MAJ, MIN, or RO (Record Only). An alarm condition
with the RO severity results in the system controller transmitting the alarm without the
severity. That is, neither MAJ (PMJ) nor MIN (PMN) is transmitted with the alarm.

The four selectable alarm relays are called Alarm Relay 1 (ALM1) through Alarm Relay 4
(ALM4). Relays are user definable in that the user may assign any combination of alarms
from a given set of alarms. The following table shows which alarms may be assigned along
with their factory default settings.

Alarms

Table C-1 shows a list of all alarms along with their descriptions, default settings, ranges
and/or severity, and affected alarm relays and LEDs.

Table C-1: Alarms, Alarm Settings, Alarm Relays and LEDs

Alarm Relays

LED

LED

Alarm / Event

Description

Default

Setting

Range /

Severity

PMJ PMN Relay

1

Relay

2

Relay

3

Relay

4

PMJ PMNNORM AUXMD

Red Yellow Green

Red

Auxiliary 1

Alarm asserted from a user configured
event on this input. The alarm can be
programmed to be asserted either on a
closure or open to Vminus. P5 on the
Distribution Module control board.

Major Major/

Minor/RO

x

x

Auxiliary 2

Alarm asserted from a user configured
event on this input. The alarm can be
programmed to be asserted either on a
closure or open to Vminus. P5 on the
Distribution Module control board.

Major Major/

Minor/RO

x

x

Auxiliary 3

Alarm asserted from a user configured
event on this input. The alarm can be
programmed to be asserted either on a
closure or open to Vminus. P5 on the
Distribution Module control board.

Major Major/

Minor/RO

x

x

Auxiliary 4

Alarm asserted from a user configured
event on this input. The alarm can be
programmed to be asserted either on a
closure or open to Vminus. P5 on the
Distribution Module control board.

Major Major/

Minor/RO

x

x