CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

60

Note: No rectifiers may be installed to the right of a Ringer Chassis.

Step Action

1.

Slide the ringer chassis into the power slot until the connector on the rear of the ringer
chassis engages with the connector at the back of the power slot on the shelf. Verify the
hook under the front left of the ringer chassis hooks under the shelf.

2.

Press down on the faceplate latch and open the faceplate. See Figure 5-16.

3.

Secure the ringer chassis to the shelf using one #4 screw, hand tight to approximately 5 in-
lbs. See Figure 5-16.

4.

Repeat until all ringer chassis’s are installed.

Figure 5-16: Ringer Chassis Installation

Step Action

5.

Locate connector on rear of ringer module and the mating connector on the inside
rear of the ringer chassis. Align the ringer module connector with the ringer
chassis connector. Place the ringer module in the guides and slide the ringer in
until it fully engages with the connector at the back of the ringer chassis.
Note: The Ringer modules install facing opposite directions. See figure 5-17.

6.

Repeat until all primary and spare ringer modules are installed.