CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

104

Reconnect Mode (Voltage); Range: Voltage, Voltage+Time
Reconnect Voltage (44.0V); Range: 39-55V
Time Delay (0 sec); Range: 0-300sec

• LVLD2 (Disabled)

Disconnect Mode (Voltage); Range: Voltage, Voltage+Time
Disconnect Voltage (442.0V); Range: 39-50V
Time Delay (0 min); Range: 0-300min
Reconnect Mode (Voltage); Range: Voltage, Voltage+Time
Reconnect Voltage (44.0V); Range: 39-55V
Time Delay (0 sec); Range: 0-300sec

• LVLD3 (Disabled)

Disconnect Mode (Voltage); Range: Voltage, Voltage+Time
Disconnect Voltage (42.0V); Range: 39-50V
Time Delay (0 min); Range: 0-300min
Reconnect Mode (Voltage); Range: Voltage, Voltage+Time
Reconnect Voltage (44.0V); Range: 39-55V
Time Delay (0 sec); Range: 0-300sec

Shutdown Alarm: The Shutdown Alarm occurs when system shutdown due to a battery
disconnect is imminent. The alarm can be enabled or disabled, and has a factory default
threshold setting of 42.0V based upon the LVBD. The alarm is issued based on the lower
disconnect threshold of the multiple contactors. This feature is factory Disabled.

Ringers: Ringer modules are an option for the CPS6000. The QS840A has the ability to
manage two ringer chassis. Configuration for the ringer settings are shown below.

Voltage

Nominal ringer output AC voltage. Range 65-100 VAC

rms

. Factory

default is 100.

Frequency

Nominal ringer output frequency. Range 15-50 Hz. Factory default is
20.

DC Offset

Enable or Disable the capability of configuring a DC offset voltage to
the Ring Output. The factory default setting is Enabled.

Redundancy

Enable or disable the loss of redundancy alarm. Alarms when one of the
two ringer modules installed in the ringer chassis is lost.