Battery Recharge Current Limit: The maximum current flowing into battery during

the recharge period is adjustable to any value between 5A and 100A, in 1A

increments. At least one battery string must be present to have this function operate.

Serial Ports

Related Commands

obj,attr Description sta

cha

ope

type range

of

values

mp1,bdr Modem

baud

rate

x x text 2400,4800,9600,19200

mp1,ins

Modem initialization string

x x text

Up to 20 characters:
“AT&FEV&C1S0=0H”

mp1,nrg

Modem number of rings before
answering

x x number 1-9 rings

mp1,hsh Modem

handshaking

x x text

“NO”: none “SW”: xon and xoff

lp1,bdr

Local RS-232 baud rate

x x text “AUTO”,2400,4800,9600,192

00

lp1,hsh Local

RS-232

handshaking

x x text

“NO”: none “SW”: xon and xoff
“HW”: cts and rts

Boost Management

Related Commands

obj,attr

description sta

cha

ope

type range

of

values

bs1,abe Auto

boost

enable

x x number 0: disable, 1: enable

bs1,tmd

Max boost duration in hours

x x number 1-80:5

Auto Boost Enable: Activates the Auto-Boost function.