GE Industrial Solutions CPS6000 User Manual
Page 177
CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 21 January 2008
177
Battery Contactor
Related Commands
obj,attr
description sta
cha
ope
type
range
of
values
cn1,dth
Low voltage battery disconnect threshold
x x number 39-48, 42 V
cn1,rth
Low voltage battery reconnect threshold
x x number 39-48, 44 V
cn2,dth
Low voltage load disconnect threshold
x x number 39-48, 42 V
cn2,rth
Low voltage load reconnect threshold
x x number 39-48, 44 V
Low Voltage Battery Disconnect Threshold: Sets the voltage at which the battery
contactor disconnects the battery strings from the load.
Low Voltage Battery Reconnect Threshold: Sets the voltage at which the battery
contactor reconnects the battery strings to the system bus voltage.
Low Voltage Load Disconnect Threshold: Sets the voltage at which the battery
contactor disconnects the battery strings from the load.
Low Voltage Load Reconnect Threshold: Sets the voltage at which the battery
contactor reconnects the battery strings to the system bus voltage.
The load disconnect feature is only supported in the Distribution Module with the
LVD contactor.