CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

177

Battery Contactor

Related Commands

obj,attr

description sta

cha

ope

type

range

of

values

cn1,dth

Low voltage battery disconnect threshold

x x number 39-48, 42 V

cn1,rth

Low voltage battery reconnect threshold

x x number 39-48, 44 V

cn2,dth

Low voltage load disconnect threshold

x x number 39-48, 42 V

cn2,rth

Low voltage load reconnect threshold

x x number 39-48, 44 V

Low Voltage Battery Disconnect Threshold: Sets the voltage at which the battery

contactor disconnects the battery strings from the load.

Low Voltage Battery Reconnect Threshold: Sets the voltage at which the battery

contactor reconnects the battery strings to the system bus voltage.

Low Voltage Load Disconnect Threshold: Sets the voltage at which the battery

contactor disconnects the battery strings from the load.

Low Voltage Load Reconnect Threshold: Sets the voltage at which the battery

contactor reconnects the battery strings to the system bus voltage.

The load disconnect feature is only supported in the Distribution Module with the

LVD contactor.