background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

32

4 Safety

Safety Statements

Please read and follow all safety instructions and warnings before installing, maintaining, or
repairing the CPS6000 System:

The CE Mark demonstrates compliance with the European Union Council Directives

for Low Voltage and EMC.

The CPS6000 platform is Underwriters Laboratories (UL) Listed per Subject Letter

1801, DC Power Distribution Centers for Telecommunications Equipment.

CPS6000 shelves equipped with QS820A ringers (in development) have hazardous

secondary voltages on the secondary bus output connectors.

Install only in restricted access areas (dedicated equipment rooms, equipment closets,

or the like) in accordance with articles 110-16, 110-17, and 110-18 of the U.S.
National Electric Code (NEC), ANSI/NFPA No. 70, and pursuant to applicable local
codes.

This equipment is to be used in controlled environments (an area where the humidity is

maintained at levels that cannot cause condensation on the equipment, the
contaminating dust is controlled, and the steady-state ambient temperature is within
the range specified).

This equipment has been evaluated for continuous use in ambient temperature from -

40°C to 75°C when used with the QS862A rectifier.

This equipment must not be installed over combustible surfaces.

For installations in the United States, Listed compression connectors are to be used to

terminate Listed field-wired conductors where required. For all installations, the
appropriate connector is to be applied only to the correct size conductor as specified
by the connector manufacturer, using only the connector manufacturer's recommended
tooling or tooling approved for that connector.

If the proper connector for the country of installation is not provided, obtain appropriate

connectors and follow manufacturer’s and all local requirements for proper
connections. All national and local rules and regulations should be followed when
making field connections.

Load connections to Bulk Output Modules should be made in close proximity to the

power shelf.

The main output voltage (48V) meets SELV requirements.