Batteries: The following battery management information is available under Status:

Installed Capacity

User entered system battery capacity in AH. Automatically entered
when using smart Lithium batteries.

On-Line Capacity

Available battery reserve from installed capacity value directly
connected to the bus. It is always the same value configured for
installed capacity except for when the smart lithium batteries are
utilized.

Current

Current flowing into or out of the batteries.

Number Of Strings

The total number of battery strings installed in the system.

Highest Temp

Highest battery temperature being measured by the thermal probes.

Temp Probes

Number of installed thermal probes.

Mid-Cell Volts

Number of installed Mid-cell voltage measurement modules.

Battery Test Result

Shows whether the most recent battery test was completed, and the
reserve time.

Next Test

The date of the next automatic battery discharge test. The automatic
discharge test feature must be enabled for this to work.

Live Reserve Time

Present value of battery reserve time calculated by the controller


Shunt Currents:

A maximum of six measured currents from each Distribution Control

and Monitoring module present in the system is displayed.

Disconnect States:

The status of the LVBD (Low Voltage Battery Disconnect) and

LVLD1-3 (Low Voltage Load) disconnects are displayed. “None” is displayed if
there are no contactors in the system.

Alarm Thresholds: Present alarm threshold settings in xx.xV format of the following system
alarms:

Float Voltage
Alarms

Very High Major, Very High Minor, BD Major and Very Low
Major

Boost Voltage
Alarms

Very High Major and High Minor

High Batt Temp

Highest temperature being measured by the thermal probes

Reserve Low

Low battery reserve time

High Ambient Temp High ambient temperature
Low Ambient Temp Low ambient temperature

Ringer Thresholds: Present status of up to two ringer chassis:

State

Ringer chassis present or not

VA

Output VA of ringer

Primary

Ringer module present in primary position

Secondary

Ringer module present in secondary/redundant position