Clear history – GE Industrial Solutions CPS6000 User Manual

Page 120

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

120

Start Battery Test

Initiates the manual battery test feature. A stop battery test operation is
displayed to interrupt the testing and return the unit to normal operation. The
manual battery test utilizes the configured test duration and a system bus
voltage threshold to represent the end of reserve.

Disconnects

Provides individual manual control of the four Low Voltage Disconnects
(LVBD, LVLD1-3) for maintenance purposes.

Enter Boost Mode

Initiates the manual battery Boos feature. A stop battery Boost operation is
displayed to interrupt the Boost operation mode and return the unit to normal
operation.

Load Factory
Defaults

This operation allows a user to bring back all factory defaults with a single
operation. Caution should be used when applying this command. Previous
configuration changes will be overwritten.

Reset Passwords

Resets user, super-user and administrator passwords back to standard defaults.

Clear History

This area of the menu system contains event history information. The controller works on a
first record in first record out once the record size of a specific field is reached. The following
system history logs are available:

Alarm History

Chronological view of the last 256 alarms and events that have occurred since
the last time the history log was cleared.

BD History

Chronological view of the last 16 battery on discharge (BD) events since the
last time the history log was cleared.

Boost History

Chronological view of the last 16 times the system entered boost mode since
the last time the history log was cleared.

Rectifier History

Chronological view of the last 256 rectifier alarms and events that have
occurred since the last time the history log was cleared.

Local Port History

Chronological view of the last local terminal logins that have occurred since
the last time the history log was cleared. The number of these events counts
towards the total number of Modem, Network, PIN, and Local port events
which can be up to 48 events.

Modem Port
History

Chronological view of the last Modem port logins that have occurred since the
last time the history log was cleared. The number of these events counts
towards the total number of Modem, Network, PIN, and Local port events
which can be up to 48 events.

PIN History

Chronological view of the last Front Panel access that required password entry.
The number of these events counts towards the total number of Modem,
Network, PIN, and Local port events which can be up to 48 events.

Network Port
History

Chronological view of the last Network access events that have occurred since
the last time the history log was cleared. The number of these events counts
towards the total number of Modem, Network, PIN, and Local port events
which can be up to 48 events.

Advertising