Appendix E: Pigtail Alarm Cable

The pigtail alarm cable plugs into the CPS6000 shelf with a J1 connector on one end and in
the CPS4000 alarm cable connector (36 pin Centronics type) on the other end. The length of
the pigtail connection is 1 foot (12 in.).

CPS4000 Side Alarm Pins

CPS6000 Alarm Pins

Pin

No

Color Office

Alarm Signal Pin

No

Office

Alarm

1 W-BL PMJ_NO

O

1 PMJ

2 BL-W PMJ_C

R

2 PMJ

3 W-O PMJ_NC

C

3 PMJ

4 O-W PMN_NO

O

4 PMN

5 W-G PMN_C

R

5 PMN

6 G-W PMN_NC

C

6 PMN

7 W-BR BD_NO

O

7 ALM1

(BD)

8 BR-W BD_C

R

8 ALM1

(BD)

9 W-S BD_NC

C

9 ALM1

(BD)

10

S-W

MJF_NO Ringer/Converter_NO

O

13

ALM3 (RFA)

11

R-BL

MJF_C Ringer/Converter_C

R

14

ALM3 (RFA)

12 BL-R MJF_NC

Ringer/Converter_NC C 15 ALM3

(RFA)

13

14

R-O

2ACF_NO/LV_NO

O

16

ALM4 (Batt Test)

15

O-R

2ACF_C/LV_C

R

17

ALM4 (Batt Test)

16

R-G

2ACF_NC/LV_NC

C

18

ALM4 (Batt Test)

17

18

19

20

21

22 S-R

ACF_NO

O

10 ALM2

(ACF)

23 BK-BL ACF_C

R

11 ALM2

(ACF)

24 BL-BK ACF_NC

C

12 ALM2

(ACF)

25

26

27

28

29

BK-BR

PBT

PBT IN

19

Plant Battery Test Input

30 Y-BL O/S_RTN

AGND 22 Protected

Analog

Ground

31

32

33

34

35

36

Advertising