CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

84

CHA NET1,IP=ddd.ddd.ddd.ddd
Verify by typing:
STA NET1,IP

• To set the Subnet mask, type:

CHA NET1,SUB=ddd.ddd.ddd.ddd
Verify by typing:
STA NET1,SUB

• Optional:

To set the Default Gateway Address, type:
CHA NET1,GTWY=ddd.ddd.ddd.ddd
Verify by typing:
STA NET1,GTWY

Optional:
To set the Host Name, type:
CHA NET1,HOST=“hostname”
Verify by typing:
STA NET1,HOST

8B

Logging out of the QS841A MCU.
To terminate the configuration session, enter the “bye” command. The
QS841A will notify the user if configuration is not complete. This message
will have the following format:

NOTICE:
Default Gateway may be required for network access.
Host Name may be required for network access.

Logging off...

Messages referencing the Gateway and Host Name are acceptable, since these
parameters are optional.

Note: If the IP address or Subnet mask messages appear, for example:

IP Address is required for network access.
Subnet mask is required for network access.

Then the configuration procedure must be repeated.

8C

Post Installation Procedure.
Once configuration has been completed

g. Disconnect the PC from the QS841A local port (RS-232)

connector J3.

h. After approximately one minute, observe the LEDs on the J3

network connector:
• Green - STATUS LED: ON
• Yellow - Link / Active LED: ON

The QS841A should be communicating over the network.