CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

30

One Ringer per Ringer Chassis is non-redundant (simplex).
Two Ringers per Ringer Chassis is 1 + 1 redundant (duplex).

Ringer

Comcode

QS820A Ringer

108990082

AC Power Cables

An ac power cable must be ordered. A standard ac cable set will not fit in the CPS6000 shelf.
Verify that the sum of the input currents for all the rectifiers served by an ac circuit breaker
does not exceed 80% of the breaker’s rating.

Table 3-A: Rectifier AC Input Current Table

Lineage

Power

Rectifier (A)

Model

Number of

Rectifier

Nominal

Input

Voltage

Number of

Rectifiers

per AC feed

Nominal AC

Current (A)

Minimum Circuit

Breaker value
recommended

(A)*

75°C Minimum

Recommended

Wire Gauge

(AWG)*

120 1 7.8

15

14

120 2 15.6 20

12

120 3 23.4 30

10

120 4 31.2 40

8

120 5 39.1 50

8

208

1

4.4

15

14

208

2

8.8

15

14

208

3

13.2

20

12

208

4

17.6

25

10

15A QS861A

208

5

22.0

30

10

208 1 6

15

14

208 2 12

15

14

208 3 18

25

10

208 4 24

30

10

20A QS852A

208 5 30

40

8

208 1 7.4

15

14

208 2 14.8 20

12

208 3 22.2 30

10

208 4 29.6 40

8

25A QS853A

208 5 37.0 50

8

120 1 13.0 20

12

120 2 26.0 35

8

120 3 39.1 50

8

208

1

8.8

15

14

208

2

17.6

25

10

208

3

26.4

35

8

25/30A QS862A

208

4

35.3

45

8

208 1 11.8 15

14

208 2 23.5 30

10

40A QS864A

208 3 35.3 45

8

208

1

14.5

20

12

50A QS865A

208

2

29.1

40

8

*Conduit and further temperature deratings may be required in some installations .Cross-check table with
local code and regulation requirements