Auxiliary Events

Related Commands

obj,attr

description sta

cha

ope

type

range

of

values

aux1-aux6,des

Auxiliary event 1-6 description

x x text up to 32 characters

aux1-aux6,ast

Auxiliary event 1-6 alarm state

x x text 0:not active, 1:active

aux1-aux6,sev

Auxiliary event 1-6 severity

x x text “MAJ”, “MIN” , or “RO”

aux1-aux6,acc

Auxiliary event 1-6 relay

x x text “R1”,“R2”,“R3”,“R4”,or

“”

The above commands facilitate assignment of the alarm relays on the controller. Refer

to Appendix C for default assignments.

Rectifier Management

Related Commands

obj,attr

description sta

cha

ope

type

range

of

values

gm1,fsp Rectifier

float

set-point

x x number 51-56.5,

54.5 V

gm1,bsp

Rectifier boost set-point

x x number 54-56.5,

55.2 V

gm1,rme

Redundancy monitor enable

x x number 0: disable, 1: enable

Rectifier Float Set-point: The voltage at which the plant will float charge the battery

strings.

Rectifier Boost Set-point: The voltage at which the plant will boost charge the

battery strings.

Redundancy Monitor Enable: Activates the Redundancy Loss alarm feature.