GE Industrial Solutions CPS6000 User Manual
Page 173
CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 21 January 2008
173
Auxiliary Events
Related Commands
obj,attr
description sta
cha
ope
type
range
of
values
aux1-aux6,des
Auxiliary event 1-6 description
x x text up to 32 characters
aux1-aux6,ast
Auxiliary event 1-6 alarm state
x x text 0:not active, 1:active
aux1-aux6,sev
Auxiliary event 1-6 severity
x x text “MAJ”, “MIN” , or “RO”
aux1-aux6,acc
Auxiliary event 1-6 relay
x x text “R1”,“R2”,“R3”,“R4”,or
“”
The above commands facilitate assignment of the alarm relays on the controller. Refer
to Appendix C for default assignments.
Rectifier Management
Related Commands
obj,attr
description sta
cha
ope
type
range
of
values
gm1,fsp Rectifier
float
set-point
x x number 51-56.5,
54.5 V
gm1,bsp
Rectifier boost set-point
x x number 54-56.5,
55.2 V
gm1,rme
Redundancy monitor enable
x x number 0: disable, 1: enable
Rectifier Float Set-point: The voltage at which the plant will float charge the battery
strings.
Rectifier Boost Set-point: The voltage at which the plant will boost charge the
battery strings.
Redundancy Monitor Enable: Activates the Redundancy Loss alarm feature.