GE Industrial Solutions CPS6000 User Manual

Page 207

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

207

The relay configuration settings on the QS840 Controller in the CPS 6000 Power System also
needs to change so that the QS840 reports alarms the same way as the CPS4000 ES648A or B
controller.

Description obj Default

ES648A

ES648B

Comments

Battery On
Discharge

bda1

R1

MAJ

R1

MAJ

R1

RO

Need to change to RO on
ES648

Very Low
Voltage

vla1

R1

MAJ

""

RO

R4

MAJ

Changes for both versions

Single AC
Fail

acf1 R2 MIN R2 MIN R2 MIN No

change

from

default

Battery Test
Active

bts1

R4

RO

""

RO

""

RO

Disable relay R4 as Battery
Test Active

Multiple
Rectifier
Failure

mrfa1

R3

MAJ

""

MAJ

""

MIN

Disable relay R3 as Multiple
Rect. Fail

Redundancy
Loss

rls1

R3

MIN

""

MIN

""

MIN

Disable relay R3 as
Redundancy Loss

Single
Rectifier Fail

rfa1

""

MAJ

""

MIN

""

MIN

Change from MAJ to MIN for
both versions

Multiple AC
Fail

macf1

R2

MAJ

R4

MAJ

""

MIN

Changes to both versions

High Battery
Temp

bta1

""

MIN

""

MAJ

""

MAJ

Change from MIN to MAJ for
both versions

Major Fuse
Alarm

faj1

""

MAJ

R3

MAJ

R3

MAJ

Relay R3 is Major Fuse alarm
for both versions

The following commands will help set up the programmable alarm relays as per the CPS4000
scheme.

No changes to default for thermal probe or contactor open alarms.

ES648A Comments

cha faj1,acc=R3

Enable relay R3 as Major Fuse Alarm

cha mrfa1,acc=""

Disable relay R3 as Multiple Rectifier Fail alarm

cha bts1,acc=""

Disable relay R4 as Plant Battery Test Active

cha macf1,acc=R4

Enable relay R4 as Multiple AC Fail

cha macf1,sev=MAJ

Multiple AC Fail is MAJ

cha vla1,acc=""

Disable relay R1 as Very Low Voltage alarm

cha vla1,sev=RO

Change Very Low Voltage alarm from MAJ to RO

cha rls1,acc=""

Disable relay R3 as Redundancy Loss

cha rfa1,sev=MIN

Change Single Rectifier Failure to MIN

cha rfa1,acc=""

Disable all relays for Single Rectifier Fail alarm

cha bta1,sev=MAJ

Change High Battery Temperature from MIN to MAJ

Advertising