GE Industrial Solutions CPS6000 User Manual

Page 168

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

168

DC Plant

Related Commands

obj,attr

description sta

cha

ope

type

range

of

values

dc1,stt Plant

state

x x text “FLOAT”,

“BOOST”

dc1,vdc Plant

voltage

x

number dd.dd V

dc1,adc

External Battery Shunt Size

x

number ddd.d A

dc1,sha1

Plant shunt size

x x number 0-9999: 200, 0: none

dc1,trd

Plant total rectifier drain

x

number ddd.d A

dc1,isd

Imminent shutdown enable

x x number 0: disable, 1: enable

dc1,cap Total

rectifier

capacity

x

number ddd.dA

dc1,rss Rectifier

restart

x x

number 0:no action 1:restart

dc1,bod Battery

on

discharge

x

number 0:on discharge, 1: not on

discharge

Plant State: The plant is normally in the float-charge mode; however, the super-user

may instruct the plant to enter the boost-charge mode.

Plant Voltage: The voltage of the plant at the time of querying.

Plant Current: The current being drawn by the load at the time of querying.

External Battery Shunt Size: External battery shunt amp rating.

Plant Total Rectifier Drain: The current being drawn by the battery and load from

the plant at the time of querying.

Imminent Shutdown Enable: Factory shipped disabled. When enabled, prior to

disconnecting of LVD contactor during battery discharge, the controller will transmit

the Imminent Shutdown alarm to the host indicating batteries will disconnect from the

load in 15 seconds. See Imminent Shutdown in Section 6 for more details on this

feature.

Total Rectifier Capacity: Sum of the rated outputs of installed rectifiers.