Page 143: Figure 10-1: ring signaling types

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

143

Types of Ringing

QS820 Ringers can be configured to provide one of three types of ringing: Battery Backed,
Ground Backed, and Ground Backed-no dc. Ringing type is selected by selecting dc Offset
polarity and by enabling or disabling dc Offset.

dc Offset polarity is set by the J12 Ringer Chassis jumper or external connection. dc Offset
may be disabled via controller setting if desired.

Volt

ag

e

Battery Backed
(Common in USA)

Ground

(VBUS+)

Ring Return

tied to VBUS+

(Tip wire)

-48Vdc

(VBUS-)

Ring

(Ring wire)

Volt

a

g

e

Ground Backed

Ground

(VBUS+)

Ring Return

tied to -48Vdc

(Tip wire)

-48Vdc

(VBUS-)

Ring

(Ring wire)

Volta

g

e

Ground Backed

No dc

Ground

(VBUS+)

Ring Return

tied to VBUS+

(Tip wire)

-48Vdc

(VBUS-)

Ring

(Ring wire)

Figure 10-1: Ring Signaling Types

Output Voltage and Frequency

Ringer output voltage and frequency settings are controlled by the Controller. See Ringer
specifications for ranges and factory settings.

Fan Power

Ringers provide power, control, and alarm monitoring for Ringer Chassis fans.