Issue 21 January 2008

85

6 AC, Alarm, and Control Cable

Reference Information

Overview

This section contains additional information (connector pin designations, etc.) that may be
required for making, customizing, or troubleshooting system connections.

AC Utility Connection

Note: Each ac connection to the CPS6000 shelf is to be provided with circuit breaker
protection at maximum 40A for a 23-inch shelf with dual ac feed and low-line (120V) input.
For high-line (200-240V) input, a 40A circuit breaker is adequate.

CAUTION: Ensure ac power is OFF to the CPS6000 system before continuing with ac
utility connection.

The 23-inch dual-feed shelf requires the H569-470 G50A ac cord, which consists of two sets
and is unterminated at the utility end. Insert these into the ac receptacles on the CPS6000
shelf. Terminate the other end with an appropriate plug. Follow all safety rules provided with
the plug when connecting the plug to the cable assembly. Refer to the following table for ac
feed polarity.

AC Voltage

120V

200 to 240V

Cable Color Code

Cable Color Code

Line 1

Line 1

Black

Brown

Neutral

Line 2 / Neutral

White

Blue

Ground Ground

Green

Green

/

Yellow

Guide the utility end of the ac cords to the utility source. When routing cable, please ensure
cable does not traverse any sharp or rough surfaces that may over time cause its insulation to
abrade. Also, please be careful to route cables away from doors and the like to prevent any
possible damage from pinching.

When connecting to utility source, ensure all local and national wiring rules are being
complied with.