Position external distribution panel – GE Industrial Solutions CPS6000 User Manual

Page 159

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

159

22-position external distribution panel

Overview

The J5694722 external distribution accepts up to 22 bullet-breakers for DC loads and
occupies 3U of vertical rack space in a 23î rack. The panel has a total output capacity of
400A and is front accessible. The following configurations are available in 3 distinct
distribution modules:

Without contactor

With 400A LVLD and 500A shunt

With 400A LVBD and 500A shunt

Features

Figure 12-7: J5694722 External Distribution

Up to 22 flexible battery positions that can be configured either with the battery bus or

the load bus using an adapter plate

All lug connections shall accept double-holed lugs.

Staggered vertical arrangement of up to three distributions directly stacked with wiring

access.

Contactor control, measurements and alarms with the QS84x compatible ES772 module

CO ground connection

Contactor options ñ None, LVBD, LVLD

500A shunt

Accommodates single, double and triple pole breakers with lug adapter for multi-pole

breakers

English hardware (1/4-20) for all customer connections

TPS fuses in place of bullet-breakers

Advertising