GE Industrial Solutions CPS6000 User Manual

Page 127

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

127

System Settings

Located here are the menus for configuring general system level settings.

Display Contrast

Allows display backlight intensity to be adjusted for contrast in local
ambient light. Factory default is 50%.

System Date and
Time

Sets system date and format. The format for date can be selected
from: mm/dd/yyyy, dd/mm/yyyy, yyyy/mm/dd, mm-dd-yyyy, yyyy-
mm-dd, dd-mm-yyyy, mm/dd/yy, yy/mm/dd, dd/mm/yy, mm-dd-yy,
yy-mm-dd, or dd-mm-yy and the format for time can be 12HR/24HR
format. The factory default is Date: mm/dd/yyyy and Time: 12HR.

Daylight Savings

Enable or disable. Factory default is Enabled.

Display T Units

°C or °F. Factory default is °C.

High Ambient T

High temperature alarm threshold that can be set from 35°C to 75°C.
The factory default setting is 75°C.

Low Ambient T

Low temperature alarm threshold that can be set from -40°C to
10°C. The factory default setting is -40°C.

Communication Ports

Menus for configuring the following communication parameters:

Port Type

Set the communication port to either Local or Modem. Factory default is
Local. This connection setting is required by the EBW in the NX400 system
in order to provide the SNMP management port.

Local Port Settings

Provides the ability to Enable or Disable Write access to the controller, the
ability to change system settings through the SNMP management or local
port. The factory default setting is enabled.

The baud rate, number of data bits, parity, number of stop bits, and flow
control parameters for the port is also configurable. These parameters have
been factory set to 9600, 8, none, 1, none, respectively, to facilitate
communication between the QS841A_NX1 and the EBW NIC.

Modem Port Settings

Provides the ability to Enable or disable Write access, the ability to change
system settings through the modem. The factory default setting is Enabled.

The baud rate, number of data bits, parity, number of stop bits, and flow
control parameters for the port is also configurable. Note: the initialization
string of the external MODEM must be set in the controller. Factory default
for the string is “AT&FEV&C1S0=0H”. This string can be modified by
utilizing EasyView or T1.317 commands through a local terminal
connection. Consult technical field support if further assistance is required.

Thee number of rings to be detected by the modem before it answers (Rings
to Answer) can be set from 1 to 9. The factory default setting is 1.