therefore:

mirc = power x recharge factor

mirc = 2725W x 1.38 = 3761W


In this high line ac example using QS862A 1635W (200-240 Vac) constant power
rectifiers, three rectifiers (3761/1635 = 2.3) are needed to support the load and recharge
the batteries within the requisite time.

Ringer and Ringer Chassis

Ringer Chassis each support one 100 VA ringing output. Redundant ringing outputs require
two Ringers in each Ringer Chassis.

Ordering Information

Ordering Guide

An ordering guide may be downloaded from the Lineage Power web site. This guide will
augment the information found here.

Note: Ordering information here is presented only from the viewpoint of miscellaneous
item ordering and may not be complete. Complete System ordering should done using
the ordering guide only.

Comcodes

The CPS6000 can be ordered by 9-digit numeric character sets called comcodes. The
following guides you through the comcode selection process in creating a power system.
Please refer to the product description section on the individual components for more details.

Power Shelves

Shelves are available in 23-inch (584 mm) and 19-inch (483 mm) rail widths. Mounting
hardware is provided. Refer to Ordering Guide for other shelf types.

Baffle

A 1U tall baffle is available to mount between shelves, below the shelf or above the shelf. See
Appendix F for application information.

Distribution Modules

The Platform has standard single slot, dual slot, front bulk and rear bulk output module
options. An external 23” distribution panel is also available for systems with the bulk output.
Battery breakers are available in lieu of the battery straps. However, maximum current
allowed through each battery breaker is 50A instead of the 100A through the battery strap.
For load breakers in a single slot distribution module, a max of two 60A load breakers can be
used. If only a single breaker is used in the topmost position, a 70A breaker may be used