Load connections – GE Industrial Solutions CPS6000 User Manual

Page 67

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

67

Load Connections

Loads can be connected using 2 bullet-style circuit breakers, GMT fuses or Direct Bus
Connections.

Double-Slot Distribution Module Note

Check if Double-Slot Distribution Module positions can be used for load positions, make
connections as described here. Positions are converted from battery to a load positions using
an adapter on the circuit breaker. This is described in the section, “Installing Circuit Breakers
and Fuses.”

Terminate Load Connections - Bullet-Style Circuit Breakers

Two Circuit Breakers can be installed in the top two positions in the Distribution Module.
The load terminals on the circuit breakers can secure cabling from 18 AWG (1mm2) to No. 2
AWG (33mm2).

Step Action

1.

Insert Load breakers in the top two positions in the Distribution Module.

2.

Terminate the load cables on the load buss with M6 nuts and torque to 65 in-lb
(7.3Nm). See Appropriate Figures 5-20a, through 5-20c for Distribution
Module connections.