GE Industrial Solutions CPS6000 User Manual
Page 188
CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 21 January 2008
188
sum
Report Battery Discharge Statistics (Profile)
Syntax:
sum dc1,bod
Description
This command reports the last battery discharge profile report. The report includes cleared date
and time, start date and time, end date and time, duration in seconds, and up to 50 sample
points. Each sample is time stamped in seconds. We compress the samples to derive a
minimum set of data required to reconstruct the curve while retaining important coup de fouet
minimum and maximum voltages and lowest voltage at end of discharge. The following is an
example of a command response:
* sum dc1,bod
:DC1 BOD
CLR=29-JUN-04,10:27:11
BEG=30-JUN-04,10:38:36
END=30-JUN-04,10:42:53
DUR=256
VAL=
0,51.08
8,50.18
18,49.24
20,48.87
248,48.36
252,49.76
254,50.84
256,51.13
.
*
The “.” line is the end-of-command identifier. The “* ” in the example above is the user
command line prompt.
GUI Report
GUI
Compatibility
Syntax:
GUI
Description
This command is for internal use only. It reports an EasyView compatibility number. The
command response is: QS840GUI=1.0