Specifications – GE Industrial Solutions CPS6000 User Manual

Page 16

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

16

Specifications

Table 2-A: CPS6000 System Specifications

Shelf

Single 19-inch or 23-inch shelf

Power Slots per Shelf

4 (19-inch shelf), 5 (23-inch shelf)

Power Units
Installed Position

5

Unit

Max. per

Shelf

Power Slots

Each

Installed from the Right

Bulk Output Module

Distribution Module

Ringer Chassis

Installed from the Left

Rectifiers

Bulk Output Module
Single-Slot Distribution Module
Double-Slot Distribution Module
Ringer Chassis
Rectifiers (19-inch shelf)
(23-inch shelf)

1
1
1
2
4
5

0
1
2
1
1
1

Rectifier Input Distribution

Dual ac input (19 and 23-inch shelves)
Individual ac input (19 and 23-inch shelves)
Single ac input (19 and 23-inch shelves)

System Architecture

Primary output: 1 primary output power bus per shelf

Primary Power Bus Current
with Bulk Output Module

19-inch shelf: 227A
23-inch shelf: 283A

Output Distribution

Primary Bus


Bulk Output Module

Single-Slot and Double-Slot

Distribution Modules

Battery connections: double-hole lugs to terminate battery
strings.

-48 Vdc bulk power outputs to loads or distribution

• Bullet-style circuit breakers

• GMT-style fuses

See Note 2.

Maximum Discharge Current

Based on rectifier capacity. See Note 2

Maximum Recharge Current

Installed shelf –48V rectifier capacity minus plant –48V load

Operating Ambient Temperature

-40 to 75 °C (-40 to 167 °F), see Note 3

Altitude

-200 to 13,000 feet (-61 to 3962 meters). See Note 4

Humidity

10% to 95% non-condensing

Audible Noise

< 60 dBA

Radiated and Conducted Emissions

FCC Part 15, Class B
EN55022 (CISPR22), Class B

Harmonics EN61000-3-2

(IEC61000-3-2)

Voltage Fluctuations

EN61000-3-3 (IEC61000-3-3)

Electromagnetic Immunity

Meets Telcordia GR-1089-CORE

Electrostatic Discharge

EN61000-4-2 Level 3

RF Immunity

IEC61000-4-3 Level 3, 10 V/m

EFT

IEC61000-4-4 Level 3, No Error; Level 4, No Damage

Surge

IEC 61000-4-5 Level 3, No Error; Level 4, No Damage

Conducted Immunity

IEC 61000-4-6 Level 3, 10V

Voltage Dips, Interruptions, and Variations IEC 61000-4-11
Earthquake Rating

Zone 4, upper floors
Underwriters Laboratories (UL) Listed per Subject Letter 1801:
Power Distribution Center for Communications Equipment, and
cUL Certified (CSA 22.2 950): Safety of Information
Technology Equipment

Safety Agency Approval

VDE licensed to VDE0805/EN60950