CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

200

Alarm Relays

LED

LED

Alarm / Event

Description

Default

Setting

Range /

Severity

PMJ PMN Relay

1

Relay

2

Relay

3

Relay

4

PMJ PMNNORM AUXMD

Red Yellow Green

Red

Open

intervention or LVD disconnect.

Manual Or
Periodic Battery
Test In Progress

Condition asserted to provide a remote
indication that a battery test has been
initiated either through automatic
means. Automatic testing must be
enabled. Factory default is disabled.

RO Major/

Minor/RO

o

Monitoring
Module Failure

Controller has detected a failure in an
attached remote monitoring module.

Minor Major/

Minor/RO

x

x

Multiple AC
Fail

Detection of two or more rectifiers
reporting ACF in the system.

Major Major/

Minor/RO

x

o

x

Multiple
Rectifier Fail

Detection of two or more rectifiers
failing in the system.

Major Major/

Minor/RO

x

o

x

Open String

Alarm issued when an external
disconnect switch produces an open
charge path to batteries in the
Distribution Module. This alarm is only
available when used with the QS872A
Board is in the system (connector P4).

Major Major/

Minor/RO

x

x

Rectifier
Redundancy
Loss

Alarm asserted when the total rectifier
output current exceeds N rectifier
capacity value. The feature must be
enabled and assumes N+1 rectifiers are
present in the system. Disabled by
default.

Disabled/
Minor

Enabled/
Disabled
(Major/
Minor/RO)

x

x

Reserve Time
Low

Reserve time low alarm threshold
configured for systems calculated back-
up reserve has been reached.

0 hours
Minor

0-99.9 hours
Major/
Minor/RO

x

x

Sense Fuse

Alarm that is automatically asserted
when the controller senses the DC bus
voltage to be lower than 35.5V +/-
0.5V.

Major Major/

Minor/RO

x

x

Single AC Fail Detection of a single rectifier reporting

ACF in the system.

Minor

Major/
Minor/RO

x

o

x

Single Rectifier
Fail

Detection of a single rectifier failing in
the system.

Minor

Major/
Minor/RO

x

o

x

Un-powered
Controller

The controller is not receiving DC
power from the shelf. All Form-C relays
are de-energized to assert respective
alarms.

N/A

N/A

x

x

x

x

x

x

Very Low Float
Voltage

The system DC output voltage has
reached a low voltage threshold
generally set below the BD threshold.
This alarm is used to indicate that the
battery reserve is depleting and the DC
voltage is approaching a critically low
output value.

46.0V
Major

40-51V
Major/
Minor/RO

x

x

Voltage
Imbalance

Alarm asserted when the controller
detects greater than 1.7V difference

Disabled/
Major

Enabled/
Disabled

x

x