CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

153

The following tables provide the pin-out definitions for J1 and J3.

Table 12-A: Connector J1 Pin-out Definitions

Pin Name

Definition

Comments/Connections

1

VPWR +

V(+) Power

Power for ES772A, connect to VBus(+)

2 N/A

Reserved

3 N/A

Reserved

4

SHUNT-

Neg Batt Shunt Input

Polarity is during battery discharge

5

BATT1_SENSE

Polarity Sense for String 1

Connect to battery negative, V(-) of String
1

6 DIST_ALM_1

Trip-Indicator

Input-1

for

US Style CB or GMT Fuse.
Alarm on closure to VBus(-
).

Connect to NC terminal of breaker micro
switch or to indicator lead of GMT fuse,
other end (C) referenced to VBus(-).

7

EXT BAT SW1

Alarm input for external
battery disconnect switch;
alarm on closure to VBus(-
).

Connect to NC micro switch of US Style
CB, other end (C) referenced to VBus(-),
micro switch must close upon manual
opening of CB.

8

VPWR -

V(-) Power

Power for ES772A, connect to VBus(-)

9

STATUS1_RTN

Reference for STATUS1

Connect to C pin of micro switch of
Contactor 1.

10 STATUS1

Contactor 1 Status Monitor

Connect to NO pin of micro switch of
Contactor 1.

11 SHUNT+

Positive Battery Shunt
Input

Polarity is during battery discharge

12 LVD1_COIL

Contactor 1 coil input

Connect to one side of Contactor 1 coil,
other side of coil connected to VBus(+).

13 DIST_ALM_2

Trip-Indicator

Input-2

for

US Style CB or GMT Fuse.
Alarm on closure to VBus(-
).

Connect to NC terminal of breaker micro
switch or to indicator lead of GMT fuse,
other end (C) referenced to VBus(-).

14 EXT BAT SW2

Alarm input for external
battery disconnect switch;
alarms on closure to
VBus(-).

Connect to NC micro switch of US Style
CB, other end (C) referenced to VBus(-),
micro switch must close upon manual
opening of CB.

Table 12-B: Connector J3 Pin Definitions

Pin Name

Definition

Comments

1

BATT2_SENSE

Polarity Sense for String 2.

Connect to battery negative VBus(-) of
string 2.

2

STATUS2_RTN

Reference for STATUS2.

Connect to C pin of micro switch of
Contactor 2.

3

STATUS2

Contactor 2 Status Monitor. Connect to NO pin of micro switch of

Contactor 2.

4

LVD2_COIL

Contactor 2 coil input.

Connect to one side of Contactor 2 coil,
other side of coil connected to VBus(+).