CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

145

Excessive Output Load: Ringer output load exceeds 100VA.

Reduced Output: Ringer provides limited ringing output at 100VA by reducing Vac as
low as 50% of Vac set point.

Hiccup: If Ringer output is overloaded to Vac less than approximately 50% of the Vac
set point, the Ringer enters the hiccup mode.

Recovery is automatic when the external fault is removed.

In this mode, the Ringer shuts-down and restarts briefly at intervals of approximately 2
minutes to test for the presence of the external fault.

Restart will cause restart immediately.

Internal Fault: Ringer output is disabled (shutdown) due to excessive temperature or
Ringer failure.

Recovery from Internal Fault

Excessive Temperature recovery is automatic when the temperature returns to a safe
value.

Ringer Failure recovery is manual, requiring one of the following:

° Removal of dc input power (remove and re-install Ringer in Ringer Chassis)

° Restart command from Controller (from front panel menu or remote)

° Ringer Failure is usually permanent and will reoccur upon completion or the

recovery attempt.