Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual

Page 101

Advertising
background image

Publication 0160-5.5 - September 1997

C-10

ODVA Interface Parameter Descriptions

ODVA Drive Profile Interface
Parameters (Continued)

Parameter

Number

Parameter

Group

Name and Description

Object

Mapping

(Class-

Instance-

Attribute)

Min./Max.

Range

Units

Factory

Default

63

Preset

[DN Preset Cmd]
This read/write parameter acts as the network preset command.

0x2A-1-192 0 to 7

Numeric
Value

0

64

Preset

[Preset RPM 0]
This read/write parameter sets the speed that the drive outputs when
selected.

0x2A-1-161 0 to 32000

1 RPM

90 RPM

65

Preset

[Preset RPM 1]
This read/write parameter sets the speed that the drive outputs when
selected.

0x2A-1-162 0 to 32000

1 RPM

600 RPM

66

Preset

[Preset RPM 2]
This read/write parameter sets the speed that the drive outputs when
selected.

0x2A-1-163 0 to 32000

1 RPM

900 RPM

67

Preset

[Preset RPM 3]
This read/write parameter sets the speed that the drive outputs when
selected.

0x2A-1-
164

0 to 32000

1 RPM

1200 RPM

68

Preset

[Preset RPM 4]
This read/write parameter sets the speed that the drive outputs when
selected.

0x2A-1-
165

0 to 32000

1 RPM

1350 RPM

69

Preset

[Preset RPM 5]
This read/write parameter sets the speed that the drive outputs when
selected.

0x2A-1-
166

0 to 32000

1 RPM

1500 RPM

70

Preset

[Preset RPM 6]
This read/write parameter sets the speed that the drive outputs when
selected.

0x2A-1-
167

0 to 32000

1 RPM

1650 RPM

71

Preset

[Preset RPM 7]
This read/write parameter sets the speed that the drive outputs when
selected.

0x2A-1-
168

0 to 32000

1 RPM

1800 RPM

72

Preset

[Accel Time 2]
This read/write parameter sets the acceleration time for parameters 68 to
71 (preset RPM 4-7).

0x2A-1-
169

100 to
65500

1ms

20000 ms

72

AC Drive
Extension

[Accel Time 2]
This read/write parameter sets the acceleration time.

0xB3-1-69

0-60000

1 ms

20000 ms

73

Preset

[Decel Time 2]
This read/write parameter sets the deceleration time for parameters 68 to
71 (preset RPM 4-7).

0x2A-1-
170

100 to
65500

1ms

20000 ms

73

AC Drive
Extension

[Decel Time 2]
This read/write parameter sets the deceleration time.

0xB3-1-70

10 to 60000 1 ms

20000 ms

This parameter applies only to the Analog Signal Follower model.

This parameter applies only to the Preset Speed model.

Advertising