Class code 0xb3 — 160 parameter table object – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual

Page 75

Advertising
background image

Publication 0160-5.5 - September 1997

B-14

DeviceNet Information

Class Code 0xB3 —
160 Parameter Table Object

Instance 1 Attributes:

Class Attributes: None Supported

Number of Instances: 1

Attribute ID

Access

Rule

Parameter Name

Data

Type

Units

Description

This Bulletin 160 SSC specific object implements all of the parameters in the 160 SSC parameter table as instance attributes of the object. For example,
attribute #1 corresponds to P01 - [Output Frequency]. This give you the ability to configure a drive via DeviceNet using attribute numbers that are pub-
lished as parameter numbers in the Bulletin 160 SSC User Manual. Important: Attributes 9 and 12 shown below do not match what is published in the Bul-
letin 160 SSC User Manual
.

01

Get

[Output Frequency]

UINT

0.1 Hz

Frequency at TB2 terminals T1, T2, T3.

02

Get

[Output Voltage]

UINT

1 Volt

Voltage at TB2 terminals T1, T2, T3.

03

Get

[Output Current]

UINT

0.01 Amperes

Current at TB2 terminals T1, T2, T3.

04

Get

[Output Power]

UINT

0.01 kW

Power at TB2 terminals T1, T2, T3.

05

Get

[Bus Voltage]

UINT

1 Volt

DC Bus voltage level.

06

Get

[Frequency Command]

UINT

0.1 Hz

Commanded frequency.

07

Get

[Last Fault]

USINT

Numeric Value

Coded last fault number.

08

Get

[Heatsink Temp]

USINT

1 C

Temperature of the drive heatsink.

09

Get

[Drive Status]

USINT

Binary Number

Status of drive in binary coded format.

10

Get

[Drive Type]

UINT

Numeric Value

Used by Allen-Bradley field service personnel.

11

Get

[Control version]

UINT

Numeric Value

version of drive firmware used.

12

Get

[Input Status]

USINT

Binary Number

Open (0) Closed (1) state of drive’s discrete inputs.

13

Get

[Power Factor Angle]

UINT

0.1

Angle (electrical degrees) between V and I.

14

Get

[Memory Probe]

UINT

Numeric Value

Used by Allen-Bradley service personnel.

16

Get

[Analog Input]

INT

0.1%

The analog input as a percent of full scale.

30

Get/Set

[Accel Time 1]

UINT

0.1 Seconds

Time to ramp from 0 Hz to maximum frequency.

31

Get/Set

[Decel Time 1]

UINT

0.1 Seconds

Time to ramp from maximum frequency to 0 Hz.

32

Get/Set

[Minimum Frequency]

USINT

1 Hz

Lowest continuous output frequency.

33

Get/Set

[Maximum Frequency]

USINT

1 Hz

Highest continuous output frequency.

34

Get/Set

[Stop Mode Select]

USINT

Numeric Value

Determines stop mode used.

35

Get/Set

[Base Frequency]

USINT

1 Hz

Set to motor’s nameplate frequency.

36

Get/Set

[Base Voltage]

UINT

1 Volt

Set to motor’s nameplate voltage.

37

Get/Set

[Max Voltage]

UINT

1 Volt

Highest voltage the drive will output.

38

Get/Set

[Boost Select]

USINT

Numeric Value

Sets the volts/Hz relationship.

!

ATTENTION: Changing this parameter
value may cause unpredictable network
conditions, resulting in equipment damage,
personal injury, or death. Ensure that you
understand how changing this parameter
affects your application.