Class code 0x29 — control supervisor object – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual

Page 71

Advertising
background image

Publication 0160-5.5 - September 1997

B-10

DeviceNet Information

Class Code 0x29 —
Control Supervisor Object

Instance 1 Attributes:

Bulletin 160 specific instance attributes.

Setting Attribute ID 100 to 0 will cause the slave to expect no control information from the master. Likewise, setting Attribute ID 101 to 0 will cause the
master to expect no status information from the slave.

Class Attributes: None Supported

Number of Instances: 1

Attribute ID

Access

Rule

Name

Data Type

Min/Max

Default

Description

3

Get/Set

RunFwd

BOOL

0 to 1

0

See page B-12.

4

Get/Set

RunRev

BOOL

0 to 1

0

See page B-12.

5

Get/Set

NetCtrl

BOOL

0 to 1

0

See page B-12.

6

Get

State

USINT

0 to 7

1 = Start-up.
3 = Ready.
4 = Enabled.
5 = Stopping.
7 = Faulted.
(See Figure B.1 on page B-11.)

7

Get

RunningFwd

BOOL

0 to 1

0

1 = (Enabled and RunFwd) or (Stopping and RunningFwd).
0 = Other State.

8

Get

RunningRev

BOOL

0 to 1

0

1 = (Enabled and RunRev) or

(Stopping and RunningRev).

0 = Other State.

9

Get

Ready

BOOL

0 to 1

1 = Ready or Enabled or Stopping .
0 = Other State.

10

Get

Faulted

BOOL

0 to 1

1 = Fault Latched.
0 = No faults present.

12

Get/Set

FaultRst

BOOL

0 to 1

0

0 -> 1 = Fault Reset.
0 = No Action.

13

Get

FaultCode

UINT

0 to 7503hex

0

In Faulted state, FaultCode indicates the fault that caused
the transition to Faulted. If not in Faulted state, FaultCode
indicates the fault that caused the last transition to the
Faulted state.
Fault codes are listed in Chapter 5.

15

Get

CtrlFromNet

USINT

0 to 1

0

Status of Run/Stop control source
0 = Control is Local.
1 = Control is from the network.

16

Get/Set

DNFaultMode

USINT

0 to 1

0

17

Get/Set

Force Fault/Trip

Boolean

0 to 1

0

0 to 1 transition forces fault.

100

➀➁

Get/Set

OutputAssembly USINT

0 to 103
(0 to 101 for
version 1.2)

20

Output Assembly instance that is currently active.

101

➀➁

Get/Set

InputAssembly

USINT

0 to 105
(0 to 102 for
version 1.2)

70

Input Assembly instance that is currently active.

102

Get/Set

DNPresetCmd

USINT

0 to 7

0

DeviceNet Preset command. (Preset Speed Units Only).

Advertising