Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual

Page 77

Advertising
background image

Publication 0160-5.5 - September 1997

B-16

DeviceNet Information

Class Code 0xB3 —
160 Parameter Table Object
(Continued)

Common Services

Attribute ID

Access

Rule

Parameter Name

Data

Type

Units

Description

64

Get/Set

[Preset Frequency 3]

UINT

0.1 Hz

Sets command frequency when selected.

65

Get/Set

[Preset Frequency 4]

UINT

0.1 Hz

Sets command frequency when selected.

66

Get/Set

[Preset Frequency 5]

UINT

0.1 Hz

Sets command frequency when selected.

67

Get/Set

[Preset Frequency 6]

UINT

0.1 Hz

Sets command frequency when selected.

68

Get/Set

[Preset Frequency 7]

UINT

0.1 Hz

Sets command frequency when selected.

69

Get/Set

[Accel Time 2]

UINT

0.1 Seconds

Sets acceleration rate for presets 4 to 7.

70

Get/Set

[Decel Time 2]

UINT

0.1 Seconds

Sets deceleration rate for presets 4 to 7.

71

Get/Set

[IR Compensation]

USINT

1%

Adds a voltage to the output based on the torque current.

72

Get/Set

[Slip Compensation]

USINT

0.1 Hz

Compensates for the inherent slip of the motor.

73

Get/Set

[Reverse Disable]

BOOL

Numeric Value

Setting to 1 disables the reverse.

74

Get/Set

[Analog Select]

BOOL

Numeric Value

Selects between unipolar and bipolar analog input.

75

Get/Set

[Analog Input Minimum]

INT

0.1%

Sets the percent of the analog input used to represent
P32 - [Minimum Frequency].

76

Get/Set

[Analog Input Maximum]

INT

0.1%

Sets the percent of the analog input used to represent
P33 - [Maximum Frequency].

78

Get/Set

[Compensation]

BOOL

Numeric Value

Setting to 1 enables the compensation.

This parameter applies only to the Analog Signal Follower model.

This parameter applies only to the Preset Speed model.

Service

Code

Implemented for:

Service

Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Advertising