Publication 0160-5.5 - September 1997

DeviceNet Parameter Descriptions

5-9

Drive Program Parameters

Below is a brief description of the Bulletin 160 SSC Interface Pro-
gram Group parameters. Refer to the Bulletin 160 SSC User Manual
for more detailed information on these parameters.

Parameter

Number

Parameter Name

Object Mapping

(Class-Instance-

Attribute)

Description

Units

30

[Accel Time 1]

0xB3-1-30

Time to ramp from 0 Hz to maximum frequency.

0.1 Seconds

31

[Decel Time 1]

0xB3-1-31

Time to ramp from maximum frequency to 0 Hz.

0.1 Seconds

32

[Minimum Frequency]

0xB3-1-32

Lowest continuous output frequency.

1 Hz

33

[Maximum Frequency]

0xB3-1-33

Highest continuous output frequency.

1 Hz

34

[Stop Mode Select]

0xB3-1-34

Determines stop mode used.

Numeric Value

35

[Base Frequency]

0xB3-1-35

Set to motor’s nameplate frequency.

1 Hz

36

[Base Voltage]

0xB3-1-36

Set to motor’s nameplate voltage.

1 Volt

37

[Max Voltage]

0xB3-1-37

Highest voltage the drive will output.

1 Volt

38

[Boost Select]

0xB3-1-38

Sets the volts/Hz relationship.

Numeric Value

39

[Skip Frequency]

0xB3-1-39

Frequency at which drive will not run continuously.

1 Hz

40

[Skip Frequency Band]

0xB3-1-40

Used with P39 - [Skip Frequency] to create skip band.

1 Hz

41

[Overload Select]

0xB3-1-41

Selects derating factor for motor overload.

Numeric Value

42

[Overload Current]

0xB3-1-42

Set to motor nameplate full load amperes.

0.01 Amperes

43

[Current Limit]

0xB3-1-43

Max output current allowed before limiting.

% I rating

44

[DC Hold Time]

0xB3-1-44

DC Injection Braking duration.

0.1 Seconds

45

[DC Hold Voltage]

0xB3-1-45

Voltage level for DC Injection Braking.

1 Volt

46

[Input Mode]

0xB3-1-46

Type of START, STOP, REV, commands.

Numeric Value

47

[Output Configure]

0xB3-1-47

Configures TB3 output relay functionality.

Numeric Value

48

[Output Threshold]

0xB3-1-48

Used in conjunction with P47 - [Output Configure].

Numeric Value

49

[PWM Frequency]

0xB3-1-49

Carrier frequency for PWM output waveform.

0.1 kHz

50

[Restart Tries]

0xB3-1-50

Times drive will attempt to reset a fault.

Numeric Value

51

[Restart Time]

0xB3-1-51

Time between restart attempts.

0.1 Seconds

52

[DB Enable]

0xB3-1-52

Enables/disables dynamic braking.

Numeric Value

53

[S-Curve]

0xB3-1-53

Enables a fixed shape S-curve.

Numeric Value

!

ATTENTION: Changing this parameter
value may cause unpredictable network
conditions, resulting in equipment damage,
personal injury, or death. Ensure that you
understand how changing this parameter
affects your application.

!

ATTENTION: Changing this parameter
value may cause unpredictable network
conditions, resulting in equipment damage,
personal injury, or death. Ensure that you
understand how changing this parameter
affects your application.