Understanding the fault led (continued) – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual

Page 59

Advertising
background image

Publication 0160-5.5 - September 1997

7-4

Troubleshooting

Understanding the FAULT LED
(Continued)

Table 2: Bulletin 160 SSC Interface Fault Codes (Continued)

Fault Code

Fault

Indication

Description

Corrective Action

50

No DeviceNet

Power

24 volt network power is not detected.

Check DeviceNet connector at Communication Module.
Also, check network’s power supply.

51

DeviceNet Module

EEPROM Fault

DeviceNet Module EEPROM has invalid data.

Reset to factory defaults P56 - [Reset Defaults].

52

DeviceNet Lost

I/O Connection

Polled I/O connection timed out.

Check DeviceNet Master for correct operation (i.e., pow-
ered up, scanner online, etc.).

53

DeviceNet Unre-

coverable Fault

No communication is occurring. Fault occurs when dupli-
cate node address exists or wrong baud rate is set.

Check DIP switch settings for proper baud rate and node
address.

54

DeviceNet Trans-

mit Fault

A transmit timeout occurred.

Power drive off and then cycle power on.

Table 3: ODVA Drive Profile Fault Codes

Fault Code

(hex)

Fault

Indication

Description

Corrective Action

1100

Max Retries Fault Drive failed to reset fault within the max retries specified. Repair system fault.

2213

Power Test

Fault detected during initial start sequence.

Check drive wiring. Check motor wiring. Reset drive to
factory defaults.

2220

Over Current

Overcurrent detected in hardware trip circuit.

Check short circuit at the drive output or excessive load
conditions at the motor.

2331

Phase U

Phase to ground fault detected between drive and motor
phase U.

Check wiring between drive and motor. Check motor for
grounded phase.

2332

Phase V

Phase to ground fault detected between drive and motor
phase V.

Check wiring between drive and motor. Check motor for
grounded phase.

2333

Phase W

Phase to ground fault detected between drive and motor
phase W.

Check wiring between drive and motor. Check motor for
grounded phase.

2341

UV Short

Excessive current has been detected between these two
drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

2342

UW Short

Excessive current has been detected between these two
drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

2343

VW Short

Excessive current has been detected between these two
drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

3120

Power Loss

DC Bus voltage remains below 85% nominal on power up
for longer than 5 seconds.

Monitor incoming AC line for low voltage or line power
interruption.

3210

Over Voltage

DC Bus maximum voltage exceeded.

Bus overvoltage caused by motor regeneration. Extend
the decel time, or install dynamic brake option or external
capacitor module.

3220

Under Voltage

DC Bus voltage fell below the minimum value while the
motor was running.

Monitor incoming AC line for low voltage or line power
interruption.