Publication 0160-5.5 - September 1997

ODVA Interface Parameter Descriptions

C-7

ODVA Drive Profile Interface
Parameters (Continued)

Parameter

Number

Parameter

Group

Name and Description

Object

Mapping

(Class-

Instance-

Attribute)

Min./Max.

Range

Units

Factory

Default

45

AC Drive
Extension

[Input Mode]
This read/write parameter configures the TB3 control inputs for either
3-wire or 2-wire run forward/run reverse control. It also enables/disables
network control of the run forward/run reverse control.
Important: Power must be cycled for the change to take effect.
0 = 3-wire control.
1 = 2-wire control.
2 = Network control.
3 = Momentary Run Forward/Run Reverse control.

0x2A-1-146 0 to 3

0

46

AC Drive
Extension

[Output Mode]
This read/write parameter configures the TB3 relay output functionality.
0 = Drive Ready/Faulted.
1 = At Frequency.
2 = Drive Running.
3 = Reverse.
4 = Motor Overload.
5 = Ramp Regulated.
6 = Above Frequency.
7 = Above Current.
8 = Above DC Bus Voltage.
9 = Retries Exhausted.

0x2A-1-147 0 to 9

Numeric
Value

0

47

AC Drive
Extension

[Output Threshold]
This read/write parameter determines the on/off point for the TB3 output
relay when P46 - [Output Mode] is set to 6, 7, or 8.

0x2A-1-148 0 to 815

Numeric
Value

0

48

AC Drive
Extension

[PWM Frequency]
This read/write parameter sets the carrier Frequency for the PWM output
waveform. The chart below provides derating guidelines based on the
PWM Frequency setting.

0x2A-1-149 2.0 to 8.0

0.1 kHz

4.0 kHz

49

AC Drive
Extension

[Restart Tries]
This read/write parameter sets the maximum number of times the drive
will attempt to reset a fault and restart the drive.

0x2A-1-150 0 to 9

Numeric
Value

0

50

AC Drive
Extension

[Restart Time]
This read/write parameter sets the time between restart attempts.

0x2A-1-151 0.5 to 300.0 0.1 Sec-

onds

10.0
Seconds

51

AC Drive
Extension

[DB Enable]
This read/write parameter enables/disables dynamic braking.
0 = Disable.
1 = Enable.
Important: This parameter can not be programmed while the drive is
running.

0x2A-1-152 0 to 1

Numeric
Value

0

!

ATTENTION: Changing this parameter value may
cause unpredictable network conditions, resulting in
equipment damage, personal injury, or death. Ensure
that you understand how changing this parameter
affects your application.