Publication 0160-5.5 - September 1997

C-2

ODVA Interface Parameter Descriptions

ODVA Drive Profile Interface
Parameters (Continued)

Parameter

Number

Parameter

Group

Name and Description

Object

Mapping

(Class-

Instance-

Attribute)

Min./Max.

Range

Units

Factory

Default

01

Motor

[Motor Rated Current]
This read/write parameter is set to the motor nameplate full load Amp rat-
ing (FLA). The drive uses this value as the motor overload setting.

0x28-1-6

0 to 24.00
Amperes

0.01
Amperes

Drive
Rating

02

Motor

[Motor Rated Volt]
This read/write parameter is set to the motor nameplate voltage. The
drive uses this value in its volts/Hz calculations.

0x28-1-7

0 to 460
Volts

1 Volt

Drive
Rating

03

Motor

[Motor Rated Frequency]
This read/write parameter is set to the motor nameplate rated Frequency.
This value is used by the drive in its volts/Hz calculations.

0x28-1-9

10 to 240
Hz

1 Hz

60
Hz

04

Motor

[Motor Base Speed]
This read/write parameter is set to the motor’s rated nameplate speed in
RPM.

0x28-1-15

200 to
32,000
RPM

1 RPM

1800
RPM

05

Control
Supervisor

[Network Control]
This read/write parameter determines whether Run/Stop control is local
(TB3) or from the network.
0 = Control from TB3.
1 = Network Control.
Important: Power must be cycled for actual control to change sources,
and actual control status is reflected in P13 - [Control From Net].

0x29-1-5

0 to 1

Numeric
Value

0

06

Control
Supervisor

[Drive State]
This read only parameter returns the status of the drive state.
1 = Startup.
3 = Ready.
4 = Enabled.
7 = Faulted.

0x29-1-6

1 to 7

Numeric
Value

07

Control
Supervisor

[Running Fwd]
This read only parameter reflects the running forward state of the drive.
1 = Drive is running forward.
0 = Drive is not running forward.

0x29-1-7

0 to 1

Numeric
Value

08

Control
Supervisor

[Running Rev]
This read only parameter reflects the running reverse state of the drive.
1 = Drive is running reverse.
0 = Drive is not running reverse.

0x29-1-8

0 to 1

Numeric
Value

Advertising