ODVA Interface Parameter Descriptions

ODVA Drive Profile Interface
Parameters (Continued)

Parameter

Number

Parameter

Group

Name and Description

Object

Mapping

(Class-

Instance-

Attribute)

Min./Max.

Range

Units

Factory

Default

37

AC Drive
Extension

[Stop Mode Select]
This read/write parameter determines the stopping mode used by the
drive when a stop is initiated.
0 = Ramp to stop.
1 = Coast to stop.
2 = DC Injection Braking.

0x2A-1-114 0 to 2

Numeric
Value

0

38

AC Drive
Extension

[Maximum Voltage]
This read/write parameter sets the highest voltage the drive will output.
Important: Must be greater than or equal to P2 - [Motor Rated Volt].

0x2A-1-137 20 to 460

1 Volt

460 or 230

39

AC Drive
Extension

[Boost Select]
This read/write parameter sets the boost voltage and redefines the Volts
per Hz curve.

0x2A-1-138 0 to 12

Numeric
Value

4

40

AC Drive
Extension

[Skip Frequency]
This read/write parameter works in conjunction with P41 - [Skip Fre-
quency Band]
to create a range of frequencies at which the drive will not
operate continuously.

0x2A-1-139 0 to 240

1 Hz

240 Hz

41

AC Drive
Extension

[Skip Frequency Band]
This read/write parameter determines the band around
P40 - [Skip Frequency]. The actual band width will be 2 times Skip Band
RPM - 1/2 the band above and 1/2 the band below. A value of zero will
disable the skip frequency.

0x2A-1-140 0 to 30

1 Hz

0 RPM

42

AC Drive
Extension

[Overload Select]
This read/write parameter selects the derating factor for the I2T overload
function.

0x2A-1-141 0 to 2

Numeric
Value

0

43

AC Drive
Extension

[DC Hold Time]
This read/write parameter defines the time that P44 - [DC Hold Volts]
voltage will be applied to the motor when P37 - [Stop Mode Select] is
set to either DC Brake or Ramp to Stop mode.

0x2A-1-144 0 to 15

1 Second

0 Seconds

44

AC Drive
Extension

[DC Hold Volts]
This read/write parameter sets the DC Voltage level applied to the motor
during braking when P77 - [Stop Mode Select] is set to either DC Brake
or Ramp to Stop mode.

0x2A-1-145 0 to 115

1 Volt

0 Volt

!

ATTENTION: Changing this parameter value may
cause unpredictable network conditions, resulting in
equipment damage, personal injury, or death. Ensure
that you understand how changing this parameter
affects your application.