Class code 0x05 — connection object – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual

Page 67

Advertising
background image

Publication 0160-5.5 - September 1997

B-6

DeviceNet Information

Class Code 0x05 —
Connection Object

Instance 1 Attributes: Explicit Message Instance

Class Attributes: None Supported

Number of Instances: 3

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

State

USINT

0 = Nonexistant
1 = Configuring
3 = Established
4 = Timed out
5 = Deferred delete (available with Commu-
nication Module version 2.00 and later)

2

Get

Instance Type

USINT

0 = Explicit Message

3

Get

Transport Class Trigger

USINT

0x83

4

Get

Produced Connection ID

USINT

10xxxxxx100 xxxxxx = Node address

5

Get

Consumed Connection ID

USINT

10xxxxxx100 xxxxxx = Node address

6

Get

Initial Comm. Characteristics

USINT

0x22

7

Get

Produced Connection Size

USINT

7

8

Get

Consumed Connection Size

USINT

7

9

Get/Set

Expected Packet Rate

UINT

Timer resolution of 10 msec.

12

Get/Set

Watchdog Action

USINT

1 = Auto delete
3 = Deferred delete (available with Commu-
nication Module version 2.00 and later)

13

Get

Produced Connection Path Length

USINT

0

14

Get

Produced Connection Path

Null (no data)

15

Get

Consumed Connection Path Length

USINT

0

16

Get

Consumed Connection Path

Null (no data)

Advertising