Publication 0160-5.5 - September 1997

B-12

DeviceNet Information

Class Code 0x29 —
Control Supervisor Object
(Continued)

Run/Stop Event Matrix

Attribute 5, NetCtrl is used to request that Run/Stop events be con-
trolled from the network. The following must occur before Run/Stop
control is accomplished from the network:

Attribute 15, CtrlFromNet is set to 1 by the device in response to
a NetCtrl request.

Power is cycled.

If attribute 15, CtrlFromNet is set to 1, the events Run and Stop are
triggered by a combination of the RunFwd and RunRev attributes as
shown in the following table.

Important: Local Stop commands from the TB3 terminal block on
the drive override Run/Stop control through DeviceNet.

Important: When attempting to use attribute 3 or 4 to start the drive,
the Explicit Message connection (Class 5, instance 1) attribute 9,
Expected Packet Rate must be set to greater than zero.

RunFwd

RunRev

Trigger Event

Run Type

0

0

Stop

NA

0 -> 1

0

Run

RunFwd

0

0 -> 1

Run

RunRev

0 -> 1

0 -> 1

No Action

NA

1

1

No Action

NA

1->0

1

Run

RunRev

1

1->0

Run

RunFwd