Publication 0160-5.5 - September 1997

C-4

ODVA Interface Parameter Descriptions

ODVA Drive Profile Interface
Parameters (Continued)

Parameter

Number

Parameter

Group

Name and Description

Object

Mapping

(Class-

Instance-

Attribute)

Min./Max.

Range

Units

Factory

Default

16

AC Drive

[At Reference]
This read only parameter is set to 1 if the drive is at its speed reference.

0x2A-1-3

0 to 1

Numeric
Value

17

AC Drive

[Network Reference]
This read/write parameter sets the type of speed reference that the drive
uses.
0 = Reference is from TB3 (analog reference or preset reference).
1 = Reference is from DeviceNet.

0x2A-1-4

0 to 1

Numeric
Value

18

AC Drive

[Drive Mode]
This read only parameter contains the drive operating mode.

0x2A-1-6

1

Numeric
Value

1 = Open
Loop
Frequency
Mode

19

AC Drive

[Speed Actual]
This read only parameter contains the actual speed command value in
RPM.

0x2A-1-7

0 to 32000

1 RPM

20

AC Drive

[Speed Reference]
This read/write parameter sets the speed reference when
P17 - [Network Ref] is set to 1.

0x2A-1-8

0 to 32000

1 RPM

1800
RPM

21

AC Drive

[Current Actual]
This read only parameter contains the actual motor current.

0x2A-1-9

0% to 200%
rated

0.01
Amperes

22

AC Drive

[Current Limit]
This read/write parameter sets the current limit for the drive.

0x2A-1-10

0% to 190%
rated

0.01
Amperes

150% rated

23

AC Drive

[Power Actual]
This read/write parameter contains the actual power in Watts.

0x2A-1-15

1 Watt

24

AC Drive

[Input Voltage]
This read only parameter contains the input voltage of the drive in volts.

0x2A-1-16

0 to 460

1 Volt

Drive
Rated V

25

AC Drive

[Output Voltage]
This read only parameter contains the output voltage of the drive in volts.

0x2A-1-17

0 to 460

1 Volt

26

AC Drive

[Accel Time]
This read/write parameter sets the time for the drive to accelerate from 0.
RPM to P29 - [High Speed Limit].

0x2A-1-18

100 to
65500

1 ms

10000 ms

27

AC Drive

[Decel Time]
This read/write parameter sets the time for the drive to decelerate from
P29 - [High Speed Limit] to 0 RPM.

0x2A-1-19

100 to
65500

1 ms

10000 ms

28

AC Drive

[Low Speed Limit]
This read/write parameter sets the lowest speed in RPM that the drive
will output continuously.

0x2A-1-20

0 to 32000

1 RPM

0 RPM