Formats (Continued)

Instance 191 Data Format (Fixed Configuration Assembly – All Preset Speed Models)

Config Num.

Parameter

Number

Description

Size

Config Num.

Parameter

Number

Description

Size

1

30

Accel Time 1

2

18

47

Output Configuration

1

2

31

Decel Time 1

2

19

48

Output Threshold

2

3

32

Minimum Frequency

1

20

49

PWM frequency

1

4

33

Maximum Frequency

2

21

50

Restart Tries

1

5

34

Stop Mode Select

1

22

51

Restart Time

2

6

35

Base Frequency

2

23

61

Preset Frequency 0

2

7

36

Base Voltage

2

24

62

Preset Frequency 1

2

8

37

Maximum Voltage

2

25

63

Preset Frequency 2

2

9

38

Boost Select

1

26

64

Preset Frequency 3

2

10

39

Skip Frequency

2

27

65

Preset Frequency 4

2

11

40

Skip Frequency Band

1

28

66

Preset Frequency 5

2

12

41

Motor Overload Select

1

29

67

Preset Frequency 6

2

13

42

Motor Overload Current

2

30

68

Preset Frequency 7

2

14

43

Current Limit

1

31

69

Accel Time 2

2

15

44

DC Hold Time

1

32

70

Decel Time 2

2

16

45

DC Hold Voltage

1

17

46

Input Mode

1

!

!

Instance 192 Data Format (Fixed Configuration Assembly – All Signal Follower Models)

Config Num.

Parameter

Number

Description

Size

Config Num.

Parameter

Number

Description

Size

1

30

Accel Time 1

2

13

42

Motor Overload Current

2

2

31

Decel Time 1

2

14

43

Current Limit

1

3

32

Minimum Frequency

1

15

44

DC Hold Time

1

4

33

Maximum Frequency

2

16

45

DC Hold Voltage

1

5

34

Stop Mode Select

1

17

46

Input Mode

1

6

35

Base Frequency

2

18

47

Output Configuration

1

7

36

Base Voltage

2

19

48

Output Threshold

2

8

37

Maximum Voltage

2

20

49

PWM frequency

1

9

38

Boost Select

1

21

50

Restart Tries

1

10

39

Skip Frequency

2

22

51

Restart Time

2

11

40

Skip Frequency Band

1

23

53

S-Curve

1

12

41

Motor Overload Select

1

!

!

!

ATTENTION: Changing this parameter value may cause unpredictable network conditions, resulting in equipment damage, personal injury, or death.
Ensure that you understand how changing this parameter affects your application.