Chapter

7

Troubleshooting

The purpose of this chapter is to help you troubleshoot your
DeviceNet Communication Module using the LEDs on the front of
the device.

Figure 7.1
Module Front View

!

ATTENTION: Servicing energized industrial control
equipment can be hazardous. Electrical shock, burns, or
unintentional actuation of controlled industrial
equipment may cause death or serious injury. Follow
the safety-related practices of NPFA 70E, Electrical
Safety for Employee Workplaces
, when working on or
near energized equipment. Do not work alone on
energized equipment.

COMM LED - Bi-colored LED (red/green) provides status information on
DeviceNet communications. The table below summarizes the operation of the
LED.

Important: When power-up occurs, the communication status LED
(COMM), flashes green for 1/4 second, red for 1/4 second, and then goes
blank while the Communication Module finishes its initialization.

COMM LED

Description

Color

State

None

No DeviceNet power or initializing.

Red

Solid

Unrecoverable fault.

Red

Flashing

I/O connection has timed out.

Green

Solid

Normal operating state.
Device is allocated to a master.

Green

Flashing

Device is on-line but not allocated to a
master.

READY LED - Green when drive is powered up.

FAULT LED - Red when drive is faulted

Off when drive not faulted.