Run mode -2 error mode -2, Modes of operation (continued) – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual

Page 25

Advertising
background image

Publication 0160-5.5 - September 1997

4-2

Modes of Operation

Modes of Operation (Continued)

Power-up Reset Mode (Continued)

If the power up or reset sequence fails, the COMM LED will go to
solid red and the module will enter the Error Mode. See the Error
Mode description in this section.

Run Mode

After a successful power-up or reset, the Communication Module
enters the run mode and operates as a slave device to a master device.
In run mode, the Communication Module:

Accepts messages from the master on the DeviceNet network.

Monitors DeviceNet incoming power.

If an error is detected, the module enters error mode. See the Error
Mode description below.

Error Mode

If the Communication Module detects an error, the COMM LED is
affected. Errors are critical or noncritical, and are summarized below

See the troubleshooting chart in Chapter 7 for details on how to
recover from an error.

Table 4: COMM LED State During Power-up Reset Mode

COMM LED State

Description

Flashes Green 1/4 sec-

ond, Red 1/4 second,

then goes blank

Occurs when power is applied to module.

Blank

Power-up initialization is taking place.

Solid Red

Indicates failed initialization or duplicate node address.

Solid Green

DeviceNet module is in the Run mode.

Table 5: COMM LED State During Error Mode

Error Type

Description

COMM LED State

Critical

(Not Recoverable)

Power-up initialization failure.

Solid Red

Duplicate node address detected.

Incorrect baud rate.

Non-Critical

(Recoverable)

I/O connection timed out.

Flashing Red

Non-Critical

(Recoverable)

DeviceNet power lost.

Off