Understanding the fault led (continued) – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual

Page 60

Advertising
background image

Publication 0160-5.5 - September 1997

Troubleshooting

7-5

Understanding the FAULT LED
(Continued)

Table 3: ODVA Drive Profile Fault Codes (Continued)

Fault Code

Fault

Indication

Description

Corrective Action

4310

Over Temperature Excessive heat detected.

Clear blocked or dirty heat sink fins. Check ambient tem-
perature. Check for blocked or non-operating fan.

5300

Drive Reset

Stop input not present.

Check stop input at TB3 terminal 8.

6310

EEPROM Fault

EEPROM has invalid data.

Reset EEPROM.

6311

DeviceNet

Module EEPROM

Fault

DevicNet Module EEPROM has invalid data.

Reset to factory defaults using P56 - [Reset Defaults].

7121

Motor Stalled

Motor has stalled. Motor load is excessive.

Longer accel time or reduced load required.

7122

Motor Overload

Internal electronic overload trip. Excessive motor load
exists.

Reduce motor load.

7421

Reprogramming

Fault

Occurs when drive parameters are reset to defaults.

Clear fault.

7500

No DeviceNet

Power

24 volt network power is not detected.

Check DeviceNet connector at Communication Module.
Also, check network’s power supply.

7501

DeviceNet Lost

I/O Connection

Polled I/O connection timed out.

Check DeviceNet Master for correct operation (i.e., pow-
ered up, scanner online, etc.).

7502

DeviceNet Unre-

coverable Fault

No communication is occurring. Fault occurs when dupli-
cate node address exists or wrong baud rate is set.

Check DIP switch settings for proper baud rate and node
address.

7503

DeviceNet Trans-

mit Fault

A transmit timeout occurred.

Power drive off, and then cycle power on.

7504

DN Forced Fault

DeviceNet module forced a fault.

Clear fault.