Class code 0x05 — connection object (continued) – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual

Page 68

Advertising
background image

Publication 0160-5.5 - September 1997

DeviceNet Information

B-7

Class Code 0x05 —
Connection Object (Continued)

Instance 2: Attributes (Polled I/O Message Connection)

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

State

USINT

0 = Nonexistant
1 = Configuring
3 = Established
4 = Timed out

2

Get

Instance Type

USINT

1 = I/O Message

3

Get

Transport Class Trigger

USINT

0x82

4

Get

Produced Connection ID

USINT

10xxxxxx100 xxxxxx = Node address

5

Get

Consumed Connection ID

USINT

10xxxxxx101 xxxxxx = Node address

6

Get

Initial Comm Characteristics

USINT

0x21

7

Get

Produced Connection Size

USINT

0 to 8

8

Get

Consumed Connection Size

USINT

0 to 4

9

Get/Set

Expected Packet Rate

USINT

Timer resolution of 10 msec.

12

Get/Set

Watchdog Action

USINT

0 = Transition to timed out
1 = Auto delete
2 = Auto reset

13

Get

Produced Connection Path Length

USINT

3

14

Get/Set

Produced Connection Path

[63hex][hex string] where [hex string] is the
input assembly number in hex

15

Get

Consumed Connection Path Length

USINT

3

16

Get/Set

Consumed Connection Path

[63hex][hex string] where [hex string] is the
output assembly number in hex

Advertising