Publication 0160-5.5 - September 1997

DeviceNet Information

B-5

Class Code 0x03 —
DeviceNet Object

Instance 1 Attributes:

Allocation_byte
Bit 0

Explicit Messaging

Bit 1

Polled I/O

Bit 4

Change of state

Bit 5

Cyclic

Common Services

Class Attributes: None Supported

Number of Instances: 1

Attribute ID

Access Rule

Name

Data Type

Value

1

Get/Set

Node Address

USINT

0 to 63

2

Get/Set

Data Rate

USINT

0 to 2

3

Get/Set

BOI

BOOL

0 = Hold in error state on BOI error
1 = Reset CAN chip on BOI error

4

Get/Set

Bus-off Counter

USINT

0 to 255

5

Get

Allocation Info

Allocation Choice
Master Node Addr

Structure of:

BYTE
USINT

Allocation_byte➀
0 to 63 = Address
255 = Unallocated

8

Get

MAC ID switch value

USINT

0 to 63

9

Get

Baud Rate switch val

USINT

0 to 3

Service

Code

Implemented for:

Service

Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

0x4B

No

Yes

Allocate_Master/Slave_Connection_Set

0x4C

No

Yes

Release_Master/Slave_Connection_Set