Procedures, Procedures -2 – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual

Page 15

Advertising
background image

Publication 0160-5.5 - September 1997

2-2

Quick Start for Experienced Users

Procedures

1.

Review Attention statements in the Preface.

2.

Check the contents of shipping box.

Unpack the shipping box making sure that the contents include:

Bulletin 160 DeviceNet module (Catalog Number 160-DN1).

10 point DeviceNet Plug.

Bulletin 160 DeviceNet Communication Module User Manual.

If the contents are incomplete, call your local Allen-Bradley representative for assistance.

3.

Ensure that the drive is correctly installed and wired.
(Stop Input (TB3-7, TB3-8) must be jumpered together
to start drive.)

Publication

160-SSC

User Manual

4.

Ensure that the DeviceNet master and network are
installed and functioning in accordance with
DeviceNet standards.

DeviceNet

Cable System Planning
and Installation Manual

(Pub. 1485-6.7.1)

5.

Remove Program Keypad Module or Ready/Fault Indi-
cating Panel from the drive.

Chapter 3

(Installation)

6.

Set the DeviceNet Module’s node address and baud
rate.

Chapter 3

(Installation)

Set the DIP Switches at the back of the module. Switches 1
through 6 control node address and switches 7 and 8 control baud
rate.

7.

Install the DeviceNet module on the drive.

Chapter 3

(Installation)

8

Wire the DeviceNet connector and plug it into the
drive.

Chapter 3

(Installation)

9.

Load the Electronic Data Sheet (EDS) file.

Chapter 6

(Using 160-DN1 with

DeviceNet Scanner, page

6-3)

Load the EDS file (Catalog # 160-EDS) in accordance with the
DeviceNet software or hardware configurator that you are using to
configure the Communication Module (see Chapter 5 for EDS file
descriptions).

DeviceNet Software

or Hardware

Configurator Manual

10.

Power up the drive and the network.

Chapter 3

(Installation)

Important: When power-up occurs, the COMM (communication
status) LED flashes green for 1/4 second, red for 1/4 second, and
then goes blank while the Communication Module finishes its ini-
tialization. If the COMM LED goes red, there is a problem.

Chapter 4

(Modes of Operation)

Chapter 7

(Troubleshooting)

11.

Configure the Bulletin 160 SSC drive for DeviceNet so
the drive can accept speed reference and control logic
via the network.

Chapter 6

(Using 160-DN1 with

DeviceNet Scanner, page

6-3 to 6-8)

Use configuration software such as DeviceNet Manager or hard-
ware such as DeviceView Hand Held DeviceNet Configurator.

12.

Configure the DeviceNet Scanner to recognize Bulletin
160 SSC drive.

Chapter 6

(Using 160-DN1 with

DeviceNet Scanner, page

6-9 to 6-15)

Use DeviceNet Manager to configure the DeviceNet Scanner’s
“Scan List” to recognize the Bulletin 160 SSC drive.