Publication 0160-5.5 - September 1997

6-2

Using 160-DN1 with DeviceNet Scanner

Needed Tools

The following tools will be needed to complete this chapter:

Bulletin 160 SSC, Series B equipped with a DeviceNet Commu-
nication Module.

SLC 500 processor with a 1747-SDN scanner.

The DeviceNet Manager Software for Windows
(Catalog 1787-MGR).

EDS files for the Bulletin 160 (Catalog 160-EDS).

Example Network

This chapter will illustrate the steps needed to configure the following
simple DeviceNet network.

Set Device MAC ID’s

Every device on a DeviceNet network must have a unique MAC ID
between 0 and 63. Setting the MAC ID on the 1747-SDN is done via
the network using the DeviceNet Manager Software. Setting the MAC
ID for the 160-DN1 may be done via DIP switches or via the network
using the DeviceNet Manager Software. For directions on setting the
160-DN1 MAC ID, refer to Chapter 3.

SLC-500 Drive & 1747-SDN

MAC ID 0

Bulletin 160-SSC

and 160-DN1

MAC ID 1

DeviceNet Manager Software

MAC ID 62