Publication 0160-5.5 - September 1997

DeviceNet Information

B-13

Class Code 0x2A —
AC Drive Object

Instance 1 Attributes:

Common Services

Class Attributes: None Supported

Number of Instances: 1

Attribute

ID

Access

Rule

Name

Data

Type

Min/Max

Units

Default

Description

3

Get

AtReference

BOOL 0 to 1

0

Set to 1 when SpeedActual is equal to SpeedRef.

4

Get/Set NetRef

BOOL 0 to 1

0

1 = Drive uses SpeedRef (attribute 8) as its speed reference.
0 = Drive gets its speed reference from local terminal block 3.

6

Get

Drive Mode

USINT 1

1

1 = Open Loop Frequency control.

7

Get

SpeedActual

INT

0 to 32000

1 RPM

0

Actual speed command in RPM.

8

Get/Set SpeedRef

INT

0 to 32000

1 RPM

1800 RPM

Network speed reference in RPM.

9

Get

CurrentActual

INT

0 to 32000

0.01 Amp

Actual motor phase current in amperes.

10

Get/Set CurrentLimit

INT

0 to 32000

0.01 Amp 200% of rating Motor phase current limit in amperes.

15

Get

PowerActual

INT

0 to 32000

1 Watt

Actual drive output power in Watts.

16

Get

InputVoltage

INT

0 to 460

1 Volt

230V or 460V Input voltage rating.

17

Get

OutputVoltage

INT

0 to 460

1 Volt

Output voltage to the motor.

18

Get/Set AccelTime

UINT

100 to 65500 1 mSec

10000

Time to accelerate from 0 to HighSpeed Limit.

19

Get/Set DecelTime

UINT

100 to 65500 1 mSec

10000

Time to decelerate from HighSpeed Limit to 0.

20

Get/Set LowSpeed Limit UINT

0 to 32000

1 RPM

0 RPM

Minimum Speed Limit.

21

Get/Set HighSpeed Limit UINT

0 to 32000

1 RPM

1800 RPM

Maximum Speed Limit.

29

Get

RefFromNet

BOOL 0 to 1

0

Status of Network Speed Reference.
1 = Drive uses SpeedRef.
0 = Drive uses local ref.

Bulletin

160 SSC

Specific

Extensions

The AC Drive Object includes in its implementation a variable number of 160 SSC specific instance attributes. By adding the number 100 to
any parameter number in the Bulletin 160 parameter table, the resulting number will be a 160 SSC specific instance attribute in the AC Drive
Object. For example, in the 160 SSC drive, parameter 5 displays Bus Voltage. Therefore, attribute # 105 of the AC Drive Object returns Bus
Voltage. This method of extending the AC Drive Object allows for an ODVA compliant implementation of the Drive Profile, and accommo-
dates all Bulletin 160 SSC models (both analog and preset speed models). Refer to the Bulletin 160 SSC User Manual, Chapter 5.

Service

Code

Implemented for:

Service

Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single