Welcome Report Control Admin

Sys Config

Tech-Ref

235

'emergency off' is performed
(i.e., being disarmed

outside

of the schedule).

This limits the time that an "Emergency Off" can
remain in effect.

- Work Late Input: When someone presses a

work-late button in this area (during the 'pre-arm
cycle), the scheduled closing time with be set as
{value selected here} from the present time.

Note: A worklate button is a custom input point with
its 'pre-process' set as "Worklate". To define a 'work
late' input-point, refer to "Input Points—Custom Point
Types", and "Input Points—Monitored Sensors".

- Limit Work Late to Midnight: User's ability to

'Work Late' (i.e., override the scheduled 'Close'
time) for this area will be limited to not extend
beyond midnight.

- Auto Arm on Fail to Close: The area will auto-

arm at the scheduled closing time. This cannot
be used in conjunction with 'Stay on Fail to Exit'
(described above).

- Transmit Fail to Close: Transmit a "Fail-to-

Close" to the monitoring station if the area has
not been armed at the scheduled closing time.

-------------------------

- Always auto disarm to Off (Blind)

(

V4.4)

:

When the area's schedule becomes active (e.g.,
start of workday), the area will fully disarm to Off
automatically. If not selected, the area will
remain armed until it is disarmed either
manually, or when someone is granted entry
(auto-disarm on valid token).

Split-Shift: If the area's schedule contains two or more
separate time intervals, the area will disarm at the
beginning of each time interval.
Also See: See the two previous fields and related
notes pertaining to "Auto-disarm on valid token..." (on
this screen/tab).

- Allow Out of Schedule Opens: Whether or not

users without 'Emergency Off' authority will be
able to gain entry and/or disarm this area
outside of its open/close schedule, and/or adjust
the area closing time (i.e., 'worklate') after their
schedule has expired. (For a non- scheduled
area, this concept does not apply, since only
'Disarm' authority would be required.)

Related Topic: "Authorities for Users/Entrants".

Auto Disarm on Valid Token Mode

(

V4.4)

- In Schedule: Sets whether or not auto-

disarming will occur for this area (see note)
while the area schedule is active, and what
arming state will be applied (per user authorities,

or 'Off' or 'Stay' regardless of the user
authorities);

Note: This pertains to the area disarming
automatically when an authorized person is granted
entry.
Unscheduled Areas: For an unscheduled area, the 'In
Schedule' selection will remain in effect 24/7 (same as
a schedule that's always active).

- Out of Schedule: Sets whether or not auto-

disarming will occur for this area (see note,
previous) after-hours (i.e., outside of the
schedule), and what arming state will be applied
(per user authorities, or 'Off' or 'Stay' regardless
of the user authorities);

Tip: The 'auto-disarm' feature can be customized for
groups of users as per their assigned 'authority'
profile.
Details: YourAccount, Authorities, (Area
Attributes), Access Schedule

Authorities for Users/Entrants

Stay-Off-Stay Scheduling

- Schedule: A schedule to be associated with

automated stay/off/stay arming in this area (also
see next setting).

Tip: Pause the mouse cursor over a schedule in the
list to see the settings for that schedule.

- Auto Stay Mode: Specifies that the area will

automatically switch from 'Stay' to 'Off', and then
'Off' to 'Stay', in-sync with schedule chosen
above. This will not occur if the area is fully
armed (ON) at the applicable times.

+ None: Disables this feature (same as selecting

"None" for the schedule.

+ Non secure Disarm to Off: The area will disarm

(e.g., at the start of the day) if it is in 'stay' mode at
the specific time;

+ Secure Disarm to Off: For the area to be

disarmed (to off) at the scheduled time, the area
must be armed to 'Stay', and it must have been fully
armed once since the last cycle (ensures someone
was in the facility to arm the area at some time);

+ Disarm to Off Pending First Valid User: The area

will disarm to off if it is in 'stay' mode at the
scheduled time, but the change will not occur until a
valid user is granted access into the area.