Interlogix VEREX Director User Manual

Page 66

Advertising
background image

58

Verex Director V4.9.1 User's Guide

21-0381E v4.9.1

the door for a duration equal to the "extended
unlock duration". This is the same as a user
who is set for "extended unlock/challenged"
gaining entry with an access card or token.

- Pending Unlock: This is an unlock command

that waits for one person to enter the facility at
the specific door.

- Grant Last User -- Reader 1 (or 2): If the last

user at a reader was denied access, this will
issue a 'Momentary Unlocking', and log that
card/user as being granted entry.

 Cards can be denied due to being expired, locked

out, wrong time, wrong door class, etc. -- as long as
they are defined in the system.

 This feature will be unavailable if someone else is

granted entry, or after 5 minutes from the time the
person was denied access (although they can
simply present their card/token again).

 This may be used in conjunction with an event-

triggered camera-view for the door (so a remote
attendant can see the person).
Related Topics: "Initial Set Up of: Views, Maps,
Cameras" (step 3b).

 This can also be used in conjunction with the pop-

up "Photo-Verification" feature (if it is set to trigger
on 'Access Denied' events).
Related Topics: Visually Verifying Users (Photo-
Verification)"

 This cannot be used (or does not apply) with:

- Cards being enrolled or disabled at a reader set to
do this (although it will apply for cards denied due
to wrong area/time, etc.);
- Access being denied due to door interlock
violations or area/disarm authority issues.

___________________________________________

Input-Point Commands

(After right-clicking a Sensor)

Also See: "Common Commands", previous/above.

-------------------------------------------------------------------------

- Bypass / Remove Bypass: "Bypass" allows

arming an area with a tripped or faulty input
point (sensor). "Remove Bypass" allows
monitoring the input point again (for a sensor
that is "OK").

____________________________________________

Output-Point Commands

(After right-clicking an Output/Device)

Also See: "Common Commands", previous/above.

--------------------------------------------------------------------------
Tips: First, select "Manual Output Control".
Additional parameters appear when applicable
(duration, etc.).

- Normal: No manual control (i.e., return to

normal operation);

- Always: Allows setting the output as On or Off

continuously (until manual control is removed);

- Momentary: Allows setting the output to

pulse/toggle once. Additional selections will
appear for:

 Whether it is to be triggered On

(high), or Off (Low);

 The state it will be left in

afterwards (Off, On, or Normal);

 How long the

relay will remain triggered (1 second to 1 week).

- Duty Cycle (1 sec. On/1 sec. off): The output

will be pulsed on and off continuously for a
selected duration (1 second to 1 week).

___________________________________________

Elevator Commands

(After right-clicking an Elevator)

Also See: "Common Commands", previous/above.

-------------------------------------------------------------------------

- Secure / Desecure: This allows applying or

removing controlled-access for all floors as
accessed from the specific elevator (lift).

(Secure: An access card or token provides access to
specific floors;

 Desecure: Anyone can access any

floor without a card or token.

Controlling a Floor (as accessed from all cabs): Refer
to "Checking Status or Controlling Floors"

Advertising