21-0381E v4.9.1

Welcome Report Control Admin

Sys Config

Tech-Ref

277

and add or select the desired output.

 Click the small [...] button to access

this screen.

 Click an "item" (such as

"unassigned") to select a new value.
(Additional items will appear as you
go along--where applicable).

Tip: See the "Item" descriptions, to
follow.

 Use the Up/Down arrows to scroll in

pop-up lists.

 Right click items to select a command

(e.g., Invert, Insert, Remove).

Note: Selections under [ More >> ] are for
reference/internal use only.

Note: This pertains to an output being triggered by a
single condition. For complex equations and 'Boolean'
operators, see "Multi-Condition Equations", to follow /
below.

Event Type: The general type of event that will

trigger the output (System, Schedule, Holiday,
Area, Point (sensor), Output, Door, Elevator (lift),
Floor, Module, or Suite-security keypad); All
function-key selections now appear under "Area".

Note: Selections appear only for device-types that
exist in your system. "System" pertains to events
associated with the specific main/system panel.
Exception: Cadence selections (at the bottom/end of
the list) enable an On/Off pulse-cycle. See
"Cadence".

Tip: To invert a function (i.e., have the output trigger
whenever something is NOT in effect), right-click the
function and select "Toggle Invert".

Target Item: This is the specific item associated

with the desired event
(e.g., Area 4, Front Door, Suite 705, Function Key
#3, etc.);

Function Keys: Since function keys 6 – 9 & 0 can be
set to require a user-PIN,
you may wish to reserve these keys for more critical
functions.

Event: This is the specific event/condition that will

trigger the output;

Output Action: This is how the output will respond

when triggered (i.e., for so many seconds, or while
the condition remains in effect, etc.).


Mapped Input (optional): Click the double-arrow

symbol to select an input point to be tripped

automatically when the event described by the
output equation occurs.

Tip: The mapped input point, in turn, can be set for
the desired signalling/reporting (and/or command)
operation like any other input point in the system.
ATTENTION: The mapping of inputs works in
parallel with normal (hard-wired) operation, such that
the input must be wired/terminated correctly (or
configured as a circuit-type that will take its present
state as 'normal').

Event Types and Events:

In general, event selections appear in plain
language, and are generally obvious in
function. Some notable exceptions and terms
are listed here:

Activity Detected / Not Detected: Pertaining to

activity detection

(

V4.2)

in an area via custom

"Activity Monitor" points, and area activity-tracking
settings.

(Ref:

 Configuration Custom Point

Type "Preprocess = Activity Monitor";
 Configuration Input Points "Point
Type = MyCustomType";

 Configuration Areas  Activity ).

Cadence selections (System - Cadence...): See

the "Cadence..." topic, to follow / below.

Counter reaches min (or max): Pertaining to user

counting

(

V4.2)

.

(Ref: Configuration Areas Counting )

.

Digital: Dial-up modem communications.
Failed to Close: A scheduled area not set to auto-

arm was not armed manually at the scheduled
time.

Force Arm: Pertaining to arming while a

point/sensor is tripped (or tampered).

Configuration Output Points [ ... ]

(Edit Output)

Items": Event Type, Target Item, Event, "", Output Action, Mapped Input