Verex Director V4.9.1 User's Guide

21-0381E v4.9.1

 Failed to Close: Area schedule expired, & no

one armed the system;

 In Window: Schedule active;

 Out Window: Schedule expired;  Pseudo: Internally
monitored conditions (Ref: Config. System

Equipment);

 Version "E": This indicates conditions

pertaining to European monitoring requirements
(requires Director

V4.2).

System

(events pertaining to the specific

main/system panel)

:

System Tone if Module Fail

Fallback sonalert (at control panel) if Module
Bus fails. Provides 1 sec. output every 8 sec.
And activates if there is no operational
keypad in an area with programmed
keypads.

System Ground

Start

Ground Start (can only be used on B004 -
main panel output 4)

System Fully

On

When system is FULLY ON

System Partially

On

When system is PARTIALLY ON (Partially or
Fully On for Europe Version)

System Fully

Off

When system is FULLY OFF

System In

Alarm

When system is IN ALARM - resets when
point(s) restore (includes pseudos &
tampers)

System Siren

Follows ALARM & FIRE siren (steady)

System Siren Fire (1 sec.)

Follows ALARM siren - steady for BURG /
EMERG and provides 1 sec on/off for FIRE
per Keypad Tone. Exception: If selected for
the siren output (#3 on main panel), this
enables UL fire-cadence: ½ sec on/off three
times, 1sec pause, and repeats.

System Siren Fire (2 sec.)

Follows ALARM siren - steady for BURG /
EMERG and provides 2 sec on/off for FIRE

System Digital

Trouble

Phone line trouble (follows report delay or
line failure)

System Was

In

Alarm

System WAS IN ALARM. This is only for
input points in alarm e.g. NOT for system
trouble (clears when alarmed areas are
turned off then back on again)

System Bypassed

When there is a point BYPASSED
somewhere in the system

System Fire

When any ‘FIRE’ point is in alarm

System Hold-Up

When any ‘HOLD UP’ point is in alarm

System Auxiliary Alert

When any ‘Aux Alert' point is in alarm

System Vault

When any ‘VAULT / SAFE’ type point is in
alarm

System Burglary

When any ‘'Burglary' point is in alarm.
Delayed burglary for European Version.

System Supervisory

When any ‘Supervisory' point is in alarm.

System Pseudo

When any 'Pseudo' condition is in effect.

System System

Trouble

Pseudo 1 – System Trouble / All type tamper
for European Version.

System Battery

Trouble

Pseudo 2 – Battery Trouble

System AC Failure

Pseudo 3 – AC (Mains) Trouble

System Phone

Line

Trouble

Pseudo 4 – Phone Trouble

System Report

Delay

Pseudo 5 – Report Delay

System Time

Lost

Pseudo 6 – Time Lost

System Time

Changed

Pseudo 7 – Time Change

System Program

Changed

Pseudo 8 – Program Change

System Program

Error

Pseudo 9 – Program Error

System Fuse

Failure

Pseudo 10 – Fuse Failure

Programmable Output Functions